Samsung VRF Service Fault Codes and Solutions

Like other air conditioners, Samsung's vrf air conditioners also have Samsung vrf error codes. Samsung vrf fault code meanings and solutions have been tried to be explained in the most appropriate way.

Fault codes are designed to indicate problems that occur in all the latest generation air conditioners. You can check the Samsung vrf air conditioner error codes from the air conditioner digital screen or the remote control screen. Samsung vrf air conditioner error codes are very easy to understand. For this reason, we recommend that you call Samsung Authorized Service and make an appointment as soon as possible in case of malfunction. Authorized Samsung service are familiar with Samsung vrf air conditioner error code problems, so they can quickly fix your problem. Otherwise, trying to fix this problem on your own may lead to more problems. If you don't want this to happen, don't try to do anything yourself.

Error code Explanation
E101-120 Indoor communication error
E121-150 Error with indoor sensor
E151-200 Other errors related to the interior
E201-209 Communication error related to outdoor unit
E210-220 MCU related control error
E221-400 Error with outdoor unit sensor
E401-550 Protect errors related to outdoor unit control / self-diagnosis
E551-600 Other faults related to the outdoor unit
E601-650 Option instrument (wired controller) related errors
E652-700 other error
P701-800 Outdoor unit control low level risk - normal closed operation
P801-900 Error with GHP-R410A, R22 outdoor unit
E901-920 Errors with hydro interior
E921-999 reserves

Edit Table

Error code ERROR MESSAGE
101 DVM, DPM, DVS: Open Unit Communication Error (Case ”: Indoor Unit Cannot Receive Communication Single: Indoor Unit Panel - Main Communication Error
102 Dış ünite -> Kapalı Birime İletişim Hatası
103 Communication error between indoor unit panel and master
104 İletişim hatası: “<_> iç ünite ise” bazıları iç ünitede (iletişim) sadece [GHP-R22] [GHP-R22] için bağlantıyı keser
105 Communication error between detection area module and indoor unit
106 Communication error between LCD and panel
Rotary Communication error between LCD outdoor unit
108 Error due to repeated address setting (when 2 or more devices have the same address in the network)
109 Communication error where indoor address is not complete. Check the communication cable between indoor and outdoor, outdoor unit quantity, indoor address setting status. Communication address not confirmed Other outdoor unit
121 Room temperature sensor error in indoor unit short/open
122 Evaporator_in Closed Unit Sensor Error Short/Open
123 Evaporator_out Indoor Unit Sensor Error/Open
124 Kapalı Birim İletişim Hatası (Kapalı Birim _> dış ünitede görüntülenen dış ünite iletişim hatası)
125 EVA_MID2 Closed Unit Sensor Short/Open
127 [GHP-R22] Indoor temperature (suction temperature) sensor separation error
128 Closed Unit Evaporator_in Sensor Deterioration
129 Closed Unit Evaporator_out Sensor Deterioration
130 Removing sensors evaporator and evaporator in indoor unit at the same time
131 Sub (Electronic) Heater Sensor 1 Error
132 Sub (Electronic) Heater Sensor 2 Error
133 Sub (Electronic) Heater Sensor 3 Error
134 Shutter sensor error (in case of model with two shutters, top error: Aurora)
gives users more mounting options. external and Perfect Fan Sensor Error
136 Shutter sensor error (model with two shutter errors at the bottom: Aurora)
137 VOC sensor open/short error
138 Gas Sensor Open/Short Error
139 ERV CO2 Sensor Open/Short Error
140 Indoor Dust Sensor Error
141 IAQ CO2 Sensor Open/Short Error
142 Indoor unit damp sensor short/open
143 Detecting Area Sensor Error
144 EVA2_IN Indoor unit's sensor short/open
145 EVA2_OUT Indoor unit short/open sensor
146 EEV input sensor short/open
147 Closed EVA2_in Sensor Break Away Error
148 Closed EVA2_OUT Sensor Break Away Error
149 AHU Master Indoor Room Sensor Setting Error
Pipe Size Ф, inch Reserved (DMS-Snet3 Error)
151 Open error of voter expansion valve in closed unit (2.)
152 Close Error of Selection Expansion Valve in Closed Unit (2.)
153 Dectect Closed float S/W 2.
154 Indoor Fan Error
155 Indoor unit fan2 error
156 Closed Unit (EEV2) Open Error 2.
157 Closed Unit (EEV2) Shutdown error 2.
158 Udoor Parent Process Error
159 Udoor low run error
161 Mixed operation error cooling and heating
162 Outdoor unit eeprom error
163 EEPROM Option Setting Error
165 Select Discharge Temp Protection Error
166 Electric motor related to wind fault
167 Closed Unit Option Dip S/W Set Failure Peripheral Peripheral
168 IAQ Security S/W Open Error
169 AHU EEV Fault Detection Error
170 Error; Fahrenheit /Celsius Degrees Use same time (closed unit choosing Celsius)
174 Erv + Heat Exchanger Inlet Temperature Sensor Short / Open
175 Open Indoor Indoor Temperature Sensor Short / Open Error
177 Emergence Signal Error in hydro box
180 MCU Left Valve Cool/Heat Simultaneously 1.
181 MCU Left Valve Cool/Heat Simultaneously 1.
185 MissConnect Power Line to Indoor Communication Line
186 SMPI (SPI) feedback error
187 K1filter feedback error
190 When checking pipe, there is no change temperature in EVA_IN or change temp eVa_in of other indoor unit
191 While checking pipe, NO CHANGE IN EVA_OUT OR CHANGED EVA_OUT OTHER CHANGE
192 Closed Unit Cover Open (Indoor Unit Switch for Safety
193 Closed panel zero crossing error
194 Closed master zero crossing fault
195 IAQ Security S/W Open Error
198 Error due to disconnected thermal fuse of indoor unit
199 Error in case of no pipe check display
201 After full tracking 5 times, missmatch of closed unit amount with those found by ODUError (some closed units disconnected communication wire, IDU powered, etc.)
202 System down due to communication error (all closed unit short)
203 External unit communication error between Main-Sub
204 After completing the monitoring 5 times, different and transmitted MCU with a set of SET MCUs
205 Communication error in all PBA in outdoor unit C-Box, Communication Wire Error Communication Error Between Outdoor unit Inv Micom-Fan Motor Micom
206 Communication error between outdoor unit Main PBA - Sub PBA
206-C001 Hub PBA Communication Error
206-C002 Fan PBA Communication Error
206-C003 Inv1 PBA Communication Error
206-C004 Inv2 PBA Communication Error
210 I can't communicate with MCU for more than 2 minutes
211 Indoor unit linked by a discontinuous Confluence kit
212 Closed unit linked with Confluence kit and setting address more than 3 overlapped
213 MCU address does not match indoor unit address
214 MCU address does not match outdoor unit address
215 Rotary switch for indoor unit address in MCU was overused between MCUs
216 Immersion switch was in position for indoor unit setting although indoor unit is not connected
217 DIP switch for indoor unit setting is out of position even if indoor unit is connected
218 The number of indoor units in the MCU is larger than the set indoor units.
219 MCU Intercooler Inlet (short or open) Error in temperature sensor located in MCU, sensor open/short
220 Error in temperature sensor located in MCU at MCU Intercooler output (short or open), via cooling sensor open/short
221 Output temperature sensor error (open/short)- Fault level: More than 4.9V (-50ºC), less than 0.4V (93ºC)
226 OUT_TECUTHE Temperature Sensor Separation Error
231 Cond_out main temperature sensor error (open/short)- Error level: More than 4.9V (-50ºC), less than 0.4V (93ºC)”
236 Cond_out Sub1 Temperature Sensor Error (Open/Short)- Fault level: 4.9V (-50ºC), less than 0.4V (93ºC)
237 Condition temperature sensor error (open/short)- Fault level: More than 4.9V (-50ºC), less than 0.4V (93ºC)
241 Cond out sensor of cond_mid or outdoor unit separation error
242 Outdoor unit heater error
246 Cond_out 1 breakup
251 PWM Discharge Temperature Sensor Error (Open/Short)- Fault Detection condition: detect outdoor temperature more than -10ºC- Fault Level: More than 4.95V (-30'c), more than 0.5V (151'c) little
256 Fixed Comp 1 DCHRG Sensor Fault (Open/Short)- Fault Detection condition: detect outdoor temperature more- Fault Level: More than 4.95V (-30'c), less than 0.5V (151'c)
257 Sabit Comp 2 DCHRG Sensör Hatası (Açık/Kısa)- Hata Tespit koşulu: dış mekan sıcaklığını -10ºC'den fazla algılayın- Hata Seviyesi: 4.95V'den (-30’c) fazla, 0.5V'den (151'c) daha az ”"
258 Fixed Comp 3 DCHRG Sensor Fault (Open/Short)- Fault Detection Condition: Outdoor Temperature Detected More Than -10ºC- Fault Level: More than 4.95V (-30'c), more than 0.5V (151'c) ) less
261 Digital Comp_Discharge Sensor Separation Error
262 FIXD Comp1_Discharge Sensor Separation Error
263 FIXD Comp2_Discharge Sensor Separation Error
264 FIXD Comp3_Discharge Sensor Separation Error
265 Dimming Temperature Sensor Separation (Main)
266 Dimming Temperature Sensor Separation (Sub1)
267 High pressure sensor separation error
268 Dimming Temperature Sensor Separation (Sub3)
269 Intake sensor separation
271 Dijital Comp Sump_Timaratür Dijital Sensör Hatası (Açık/Kısa)- Hata Tespit koşulu: dış mekan sıcaklığını tespit edin -10ºC- Hata Seviyesi: 4.95V'den (-30’c) fazla, 0.5V'den (151'c) daha az ”"
276 Sabit COMP1 SUMP_TEMARATUTE Sensör Hatası (Açık/Kısa)- Hata Tespit koşulu: dış mekan sıcaklığını -10ºC'den fazla algılayın- Hata Seviyesi: 4.95V'den (-30’c) fazla, 0.5V'den (151'c) daha az ”"
277 Sabit Comp2 Sump_Tezural Sensör Hatası (Açık/Kısa)- Hata Tespit koşulu: dış mekan sıcaklığını tespit edin -10ºC- Hata Seviyesi: 4.95V'den (-30’c) fazla, 0.5V'den (151'c) daha az ”"
278 Fixed COMP3 SUMP_TEMARATURE Fixed 3 Sensor Fault (Open/Short)- Fault Detection condition: detect outdoor temperature more than -10ºC- Fault Level: More than 4.95V (-30'c), more than 0.5V (151'c) ) less
291 High Pressure Sensor Error (Open/Short) Only when running Comp, detect (SHORTERROR: less than 0.4V, error detection), (OpenError: more than 4.2V, error detection)
296 Low Pressure Sensor Error (Open/Short) Only when running Comp, detect (SHORTERROR: less than 0.4V, error detection), (OpenError: more than 4.7V, error detection)
301 High pressure sensor separation error
306 Low Pressure Sensor Separation Error
307 Oil Balance Sensor Short/Open
308 Suction sensor short/open
309 Oil Balace Sensor2 Sensor Short/Open
310 Oil balance sensor3Sensor short/open
311 Double pipe sensor short/open
312 Main cooling left valve open error
313 4-way valve operating error
314 Oil Balace Sensor 4 Short/Open
315 CT1 sensor short or open
316 CT2 sensor short or open
317 CT3 sensor short or open
320 OLP sensor short / open
321 Evi Input Sensor Short/Open
322 Evi Outlet Sensor Short/Open
323 Suction sensor 2 fault (short or open
324 Outdoor fan motor current sensor short / open
325 Outdoor fan2 motor current sensor short / open
330 Outdoor Plumbing Input Sensor Out 0 Time (TA_0)
331 Inlet pipe (TA_1) outdoor sensor out
332 2, Inlet Pipe outdoor sensor out (TA_2)
333 Three times the inlet pipe outdoor sensor (TA_3)
334 Four times the inlet pipe sensor outdoor (TA_4)
335 Outdoor Pipe Outlet Sensor Out 0 Time (TB_0)
336 1 Outdoor Sensor Out Pipe Outlet (TB_1)
337 Outdoor sensor twice pipe output (TB_2)
338 Outdoor Sensor Three times pipe outlet (TB_3)
339 Outdoor sensor four pipe outlets (TB_4)
346 Error2 due to operating failure of FAN2
347 Motor wire of FAN2 is not connected
348 Lock error on fan2 of outdoor unit
353 Error due to overheated motor of Outort Unit's FAN2
355 Error due to overheating IPM of Fan2.
361 2 CT1 Inverter Compressor Start Fault or Low Current
364 Error due to overcurrent of the inverter compressor.
365 V-limit fault of inverter compressor 2. 2 Inverter compressor overload stops (30A or more).
366 Error due to overvoltage/undervoltage of inverter PBA2. Connection voltage less than 2 DC 150V 410V inverter.
367 Error due to disconnected wire of compressor 2. Dependence of 2 wires or inverter compressor rotation on compressor
368 Output current sensor error of inverter PBA2. 2 Comp Inverter current sensor error.
369 DC voltage sensor inverter PBA2. 2 DC Link Inverter Sensor Error.
371 2 Inverter outdoor unit EEPROM Read/Write Error (OTP error)
374 Heat Sink Temperature Sensor Inverter PBA2. 2 Inverter Heat Sink Temperature Sensor Error.
378 Fan2's Hall IC Connection Error. Open Fan 2 IPM H/W OC
385 Error due to inverter 2 input current. 2 Inverter input current sensor error.
386 Fan2 overvoltage/undervoltage error
387 Open Fan 2 Hall Sensor Error
389 V-Limit error on Fan2 of the compressor
391 Fan Controller 2 EEPROM Read/Write Error
393 FAN2's output current sensor error. Fan Controller 2 Current sensor error.
396 FAN2's DC voltage sensor error. Fan Controller 2 DC Link Sensor Error.
399 Heat Sink Temperature Sensor Fan2. 2 Fan Controller Cooling Temp Temperature Sensor Error.
400 Error due to overheating due to contact error in IPM of inverter PBA2
401 Outdoor freezer detection 1
402 Outdoor freezer detection 2
403 Outdoor Freeze Detection 3 - Freeze Comp Down
404 Outdoor overload 1 protection control fault
405 Outdoor overload 2 protection control fault
406 Outdoor overload 3 protection control error
407 Comp Down due to high pressure protection control
408 High pressure protection control 2
409 Comp Down 3 due to High Pressure Protection Control
410 Comp Down due to low pressure sensor protection control
411 Comp down due to low pressure protection control
412 Comp Down 3 due to low pressure sensor protection control
413 Outdoor Wife Down_1 Protection Control
414 Outdoor Wife Down_2 Protection Control
415 Outdoor Wife Down_3 Protection Control
416 Outdoor Durability Temperature _1 Protection Control
417 Outdoor Durability Temperature _2 Protection Control
418 Outdoor Durability Temperature _3 Protection Control
419 Outdoor EEV#1 boot 6. Self check error
420 Outdoor EEV#2 Power On 6. Self Check Error
421 Outdoor EEV#3 Power On 6. Self check error
422 Outdoor EEV#1 Shutdown 6. Self Check Error
423 Outdoor EEV#2 Shutdown 6. Self-check error
424 Outdoor EEV#3 Shutdown 6. Self-check error
425 Outdoor reverse phase or missing phase detect 1 error
426 Outdoor reverse phase or missing phase detection 2 error
427 Outdoor reverse phase or missing phase detection 3 error
428 Compression ratio control error 1
429 Compression ratio control error 2
430 Comp with compression ratio control error
431 Oil Balance Valve1 Error
432 Oil Balance Valve2 Error
433 Oil Balance Valve 3 Error
434 Oil Balance Valve Opening Error (DVM Plus 2, Hotgasvalve Opening Error)
435 Water Cooling Flow Switch Error
436 Protection for evaporator freeze and burst failure
437 Oil Balance Valve Closing Error (DVM Plus 2, Hotgasvalve Opening Error)
438 Evi eev opening error
439 Error due to refrigerant leak
440 Heat mode operation prohibited when outside temperature is above 30ºC
441 -5ºC'den daha az IA IA IA IA IA
442 Prohibit an operation during heat mode with refrigerant charge operation when the door temperature is above 15ºC
443 Before cooling, less than 1K with low pressure (no restart)
445 CCH is self-contained. CCH Self-check error (CCH failure or snowfall sensor MISS connection).
446 Error due to operation failure of Fan1. Maneuvering fan controller 1 fan failed.
447 The motor wire of FAN1 is not connected. Fan Controller Wiring 1-Wire USA
448 Lock error on fan1. Fan Controller 1 Lock error.
450 High temperature every time (protection control)
451 Low Pressure Switch Low Pressure (Protection Control)
452 Instant Power Off Error (Delete when Comp is reworked) Open air zero crossing error
453 Outdoor fan high temperature error
454 Outdoorfan RPM error (more than 2500rpm and the difference comparing target speed with practical speed is more than 10 seconds more than 10 seconds).
455 OutoorFan IPM (internal PCB module) High temperature error
456 Outoorfan overcurrent fault
457 Outdoorfan reversed the opposite direction of the wind fault
458 CT1 via outdoor unit fan (fan error) or money
459 Outdoor unit IPM fault error or CT2 via para
460 Outdoor unit communication power disconnected detection or via CT3 currency
461 Inverter Comp Operating Error or CT1 Low Currency
462 All Currency Check Comp Stop or CT2 Low Currency
463 OLP Temperature Control Comp Stop or CT3 Low Currency
464 DC Peak Comp Stop
465 Comp overload stop (above 30A)
466 DC Link Voltage less than 150V, over 410V
467 CONP Revolute Error or Comp Wire In Link
468 Inv Comp Current Sensor Error
469 DC link sensor error
470 Outdoor unit eeprom read/write error
471 Outdoor unit eeprom read/write error (OTP error)
472 Outdoor unit zero crossing error
473 Inverter Comp Lock Error
474 Heat Sink Temperature Sensor Inverter PBA1 Error
475 Outdoor unit bldc fan 2 error or AutoorFAN2 RPM error (more than 2500RPM and the difference comparing target speed with practical speed is more than 10 seconds more than 10 seconds).
476 4way fault detection
477 Control for preservation of liquid refiggeran
478 Error due to overcurrent of Fan1. Outdoorfan IPM H/W OC.
479 4way Miss Connection Detection Error
480 Fixed Comp 1 STEGE OLP Protection Check (Leak for Heatsink Error)
481 Comp1 Operating Error
482 Comp2 Operating Error
483 Overvoltage of H/W DC link
484 PFC overload (overcurrent) error
485 Inverter 1. Error due to Input Current. Current sensor error.
486 Error due to overvoltage/undervoltage of fan. Open Fan DC-Link Voltage Under/Over Error.
487 Fan1's Hall IC error. Open Fan Hall Sensor Error.
489 V-Limit error on Fan1 of the compressor
490 Outdoor Temperature 0 Deegree and Indoor Temperature Less Than 0 Forbidden Forbidden To Work
491 Fan controller1 eeprom read/write error
492 On Fan2 IPM H/W OC
493 Fan1 output current sensor error. Fan controller1 Current sensor error.
494 Delayed time error due to OutoorFAN2 fan error
495 Outdoor fan2 overheat error
496 Fan1's DC voltage sensor error. Fan Controller1 DC Link Sensor Error.
497 Outdoor fan2 overcurrent error
498 Open Fan2 IPM (internal PCB module) Overheat error
499 Fan1's Heat Sink Temperature Sensor Error. Fan Controller1 Heat Sink Temperature Sensor Error.
500 IPM overheat error for Inverter Comp
503 Error due to warning user to check if service valve is closed
504 Error due to self-diagnosis of compressor operation
505 Error due to self-diagnosis of the high pressure sensor
506 Error due to self-diagnosis of the low pressure sensor
512 Reserved (DMS-Snet3 Error)
551 Working on Ice
552 Low discharge pressure
553 equality operation
554 Loading_failure / total leakage of refrigerant of outdoor unit
555 Recovery of oil
556 Outoor Unit Power Set Option Error
557 When in DPM mode, the product option is not the same between off units
559 Indoor unit operation stop due to detecting unknown error in outdoor unit
560 Outdoor unit switch option setting error (not implemented)
561 Outdoor unit h (supply air) fan rpm
562 Outdoor unit ra (room air) fan rpm
563 indoor unit mixed installation error
564 IAQ Clean Fan Error
565 Connection Error Between COMP and Power Wire - Power Line of EVA1 Connect with power line of Comp2 or EVA2 Connect with Comp1
570 Boot Code Check Failed
573 Error due to use of one type of open unit in module installation
574 Total leakage of refrigerant of outdoor unit 2
575 Total leak of refrigerant of outdoor unit 3 (Comp1, Comp2 bot detected)
601 Kablolu LCD (Denetleyici) <_> İç ünite iletişim hatası
602 Ana Tel LCD <_> Köle Teli LCD İletişim Hatası
603 Communication Pack Error (BaudRate / Different Communication Type)
604 Kablolu LCD (Denetleyici) <_> İç ünite izleme hatası 10 defadan fazla
605 7 Günlük Zamanlayıcı <_> Tel LCD, CAUR İletişim Hatası
606 Wire LCD COM1/COM2 Cross Installation Error
607 Wile Wire LCD Master-Master setup, communication error
608 No external link erv controller setup error
609 No external link indoor setup error
610 CAUR <_> Verici İletişim Hatası
611 DMS <_> CAUR İletişim Hatası
612 DMS <_> Peak Verici İletişim Hatası
613 DMS <_> PIM/SIM Verici İletişim Hatası
614 Eletricity Syste miktarı <_> PIM/SIM Verici İletişim Hatası
615 Verici <_> İç ünite iletişim hatası (tam verici izlemeden sonra, 2 dakika için bazı iç ünite iletişim kuramaz.)
616 Verici <_> Dış ünite iletişim hatası (CompleteTransMitter izlemeden sonra, 2 dakika açık ünite için iletişim kuramıyor)
617 Tepe Güç Verici <-> Talep Denetleyicisi İletişim Hatası, Talep Verici<--> Eletricity sistemi iletişim hatası miktarı
618 ERV Controller+One Closed Unit (16EA) Maximum Load Number Error
619 Celsius/Fahrenheit Indoor Unit Mixed Installation Error (New Wire LCD, outside of indoor unit connected with “Celsius/Fahrenheit” indoor unit mixed installation)
620 New wire remote “Celsius/Fahrenheit” Set error (DIP S/W #4 SET ERROR)
621 New Wire Remote Controller Master/Slave Dip Switch Option Setting Error (Difference with Master and Slave Set Option)
622 Select Demand Controller / Electrical System Fault Type
623 Requestor PT / CT Ratio Set Error
624 Requestor Data Get Error From Electricity Quantity
625 MasterDMS? Slave DMS communication error
626 ERV Jumper Remote Controller (AWR-WE00) ERV Separate Installation Error (Not Connecting a Closed Unit and Erv Only Installed) Indoor Jumper Remocontroller (AWR-VH10) Indoor Unit Separate Installation Error (Only ERV Link not installed)
627 Connection Control In Master/Slave Wire Remote Controller, Slave Wire remote controller 2EA setup error (at the same time installing cable refocus kit on main wire remocontroller 2EA)
628 DMS <_> Verici İletişim Hatası
629 DMS <_> DDC iletişim hatası
630 ERV Wire Remote Controller Normal Ventilation Option Setting Error - Check normal ventilation option only. - ERV Normal Ventilation No Option, Use Wire Remote Controller Option Normal Ventilation
631 Ervwire remote auto vent option setting error- Set auto vent only- ERV Auto Vent No Option, Use Wire Remote Controller Auto Vent
632 Error1 when pulse input except setting value of pulse width by PIM. Less than 20ms, 2. More than 400ms, 3. Set pulse width range, 4. Bag repeated for 3 minutes
652 Com 1 Dual Master setup communication error
653 Temperature Sensor Open/Short Error
654 Frame fault or damper fault (ERV model)
655 Reserved (DMS-Snet3 Error)
656 Reserved (DMS-Snet3error)
701 1. swimming
702 Indoor eev 1st clsing
703 Closed EEV opening 1.
720 Outdoor EEV#1 Power On Self check fails every time
721 Outdoor EEV#2 Power On Self Check Error
722 Outdoor EEV#3 Power On Self check fails every time
723 Outdoor EEV#1 Shutdown Self check every time
724 Outdoor EEV#2 Shutdown Self check every time
725 Outdoor EEV#3 Shutdown Self check every time
768 Reserved (DMS-Snet3)
801 [GHP-R410A] İletişim hatası: “<_> dış ünite ise”: Bağlantı kesme
802 [GHP-R410A] İletişim Hatası: “Açık Bir Ünite <_> IF”: Bağlantı kesme
803 [GHP-R410A] İletişim hatası: “<_> İç ünite ise” iç bir ünitede bazı bağlantılar (iletişim)
804 [GHP-R410A] Communication error: between outdoor unit
805 [GHP-R410A] Error setting outdoor unit organization
806 [GHP-R410A] Remocon sensor connection/short circuit
807 [GHP-R410A] Open Liquid Pipe Sensor Connection/Short Circuit
808 [GHP -R410A] Outdoor Unit - Subcooling Heat Exchanger Input Temp Thermystor Connection/Short Circuit
809 [GHP-R410A] Comp Emponction Temperature overheating
810 [GHP-R410A] Comp Emponction Super-It-It-Itoat Soar
811 [GHP-R410A] refrigerant high pressure switch connection
812 [GHP-R410A] Gas EEV output error
813 [GHP-R410A] Refrigerant low pressure sensor error (2.)
814 [GHP-R410A] Refrigerant high pressure sensor error 1
815 [GHP-R410A] Refrigerant high pressure sensor error 2 (value of high pressure sensor lower than standard low pressure)
816 [GHP-R410A] Water pump operation error
817 [GHP-R410A] Water Pump A series of cycle errors
818 [GHP-R410A] IPM (outdoor unit fan operating driver) Error
819 [GHP-R410A] Outdoor Heat Exchange Fan 1 Operation Malfunction
820 [GHP-R410A] Outdoor Heat Exchange Fan 2 Operation Error
821 [GHP-R410A] Outdoor Heat Exchange Fan 3 Operation Malfunction
822 [GHP-R410A] Outdoor Heat Exchange Fan 1 A series of speed error
823 [GHP-R410A] Outdoor Heat Exchange Fan 2 A Series of Revolute Errors
824 [GHP-R410A] Outdoor Heat Exchange Fan 3 A Series of Revolute Errors
825 [GHP -R410A] Outdoor Unit - Heat Exchange Fan Error
826 [GHP -R410A] Outdoor Unit - Accum Exit Temp Thermystor 1 Disconnect/Short Circuit
827 [GHP -R410A] Open Unit - Accum Exit Temp Thermystor 2 Disconnect/Short Circuit
828 [GHP -R410A] An Open Unit - Refrigerant Lower Pressure Switch Connection
829 [GHP-R410A] Refrigerant low pressure error
830 [GHP-R410A] Three-phase fault
831 [GHP-R410A] One phase power part fault
832 [GHP -R410A] Main - Sub Micom Program Version Unique
833 [GHP-R410A] Via indoor unit connection number
834 [GHP-R410A] Via indoor unit connection capacity
835 [GHP-R410A] Outdoor indoor connection match
836 [GHP -R410A] Outdoor unit -goal control
837 [GHP-R410A] Refrigerant high pressure error 1
838 [GHP-R410A] Refrigerant high pressure fault 2
841 [GHP-R410A] Outdoor Unit Gas Temp Thermistor Short/Disconnect
843 [GHP-R410A] Engine coolant temperature sensor short/disconnect
844 [GHP-R410A] Motor discharge temperature sensor connection
845 [GHP-R410A] Engine fluid pressure error
846 [GHP-R410A] Engine fluid pressure switch disconnected
847 [GHP-R410A] Engine on Revolute 1
848 [GHP-R410A] Engine on Revolute 2
849 [GHP-R410A] Startup Error
850 [GHP-R410A] Motor A series of speed control errors
851 [GHP-R410A] Engine Stall
852 [GHP-R410A] igunaita (igniter) Low voltage
853 [GHP-R410A] IGUNAITA (FIRER) Connection
854 [GHP-R410A] Igunaita (Four) Voltage
855 [GHP-R410A] Motor discharge temperature error
856 [GHP-R410A] Engine coolant temperature overheat
857 [GHP-R410A] Motor operation error
858 [GHP-R410A] Engine cooling
859 [GHP-R410A] Engine underrun revolution
860 [GHP-R410A] Engine A Series of Revolute Haunting Errors
861 [GHP-R410A] Comp Discharge Temperature Overheat
862 [GHP-R410A] Compressor Discharge Temperature Sensor 1 Short/Disconnect
863 [GHP-R410A] Compressor Discharge Temperature Sensor2 Short/Disconnect
864 [GHP-R410A] Compressor Discharge Temperature Sensor 3 Short/Disconnect
865 [GHP-R410A] Compressor discharge temperature sensor 4 short/connection
866 [GHP-R410A] Compressor NHALE Temperature Sensor1 Short/Disconnect
867 [GHP-R410A] Compressor suction temperature sensor2 short/connection
868 [GHP -R22] An Open Unit - Accumulation Inlet Temperature Sensor Short/Disconnect
869 [GHP -R22] Open unit - Refrigerants gas pipe temperature sensor short/disconnect
870 [GHP -R22] Open unit - Comp Lubricating Oil Shortage Error
871 [GHP -R22] Open unit - Refrigerant overcharge error
872 [GHP -R22] Open unit - Compressor induction temperature error
873 [GHP-R22] Engine Cooling System Error
874 [GHP-R22] Engine Oil System Error
875 [GHP-R22] Motor Power System Error
876 [GHP-R22] Engine Run/Control System Error
880 [GHP -R410A] Open unit - Engine Coolant Low
881 [GHP -R410A] Open unit - Engine Oil Leak
882 [GHP -R410A] Open unit - Lack of comp oil
883 [GHP -R410A] Outdoor unit - Start Trans Voltage Short
901 Water inlet sensor (TW1) Short / open
902 Water Outlet Sensor (TW3) Short / Open
903 PHE sensor (TW2) Short / open
904 Water tank sensor short / open
905 Sun sensor short / open
911 Stream SWTICH Open Error
912 Flow SWTICH Shutdown Error
UP Trial completed (unprepared) - Will clear after trial run for 1 hour or auto-review complete